TM 5-3610-287-24
2-51.
REPAIR LOAD CENTER (CONT)
WARNING
Pay careful attention when tagging cables and wires on main
power receptacle. Cables and wires on new receptacle must
be installed in exactly the same order as on old receptacle.
Failure to observe this warning may result in death or
serious injury.
Tag wires (5), loosen screws (6) , remove wires (5), and pull through
4.
conduit (7).
Tag main power receptacle cables (8) and power monitor assembly
5.
wires (9). Loosen screws (10) and remove-wires (9) and cables (8).
Pull cables (8) through conduit (11).
6.
Loosen screw (12), remove white grounding cable (13), and pull through
7.
conduits (7) and (11).
Tag and remove wires (14) from exterior receptacle (15). Pull wires
8.
(14) through conduits (11) and (7).
Loosen screw (16), remove green ground wire (17), and pull through
9.
conduits (7) and (11).
10.
Remove segmented locknut (18) and conduit (11).
11.
Remove plug (19) from conduit (7).
12.
Remove screws (20) and main power switch (21).
13.
Install new main power switch (21) with screws (20).
14.
Install plug (19) in conduit (7).
15.
Install conduit (11) with segmented locknut (18).
Cables and wires on new main power switch must be installed
in exactly the same order as on old switch. Failure to
observe this warning may result in death or serious injury.
Feed green ground wire (17) through conduits (11) and (7) and install
16.
with screw (16).
Feed wires (14) through conduits (7) and (11) connect to exterior
17.
receptacle (15).