TM 5-3610-287-24
2-50.
REPAIR POWER MONITOR ASSEMBLY (CONT)
Install standoffs (6) on new circuit card assembly (4) with screws (5)
6.
and lockwashers.
7.
Install wires (7) on circuit card assembly (4).
8.
Install circuit card assembly (4) with screws (3) and lockwashers.
9.
Install power monitor assembly (2) with hex bolts (1), lockwashers,
and flatwashers.
WARNING
ELECTRICAL HAZARD. Do not connect power cable to Section
before grounding. Failure to observe this warning may
result in death or serious injury.
10.
Ground Section and connect main power cable.
11.
Test operate by checking for correct phase and voltage (TM 5-3610-
12.
Set MAIN POWER switch to ON.
Load center is repaired by replacing: a. 110-Volt circuit breaker
b. 12-Volt circuit breaker c. Main power switch
110-VOLT CIRCUIT BREAKER
INITIAL SETUP
Tools
Light machine repair tool kit (appendix B, section III, item 11)
Flat-tip screwdriver
Extension light
Materials/Parts
GFI circuit breaker, QF-120
Main circuit breaker, Q3100
70 Amp circuit breaker, 3 pole, Q370
20 Amp circuit breaker, 3 pole, Q320
20 Amp circuit breaker, 2 pole, Q220
20 Amp dual circuit breaker, Q2020
20 Amp circuit breaker, Q120
15 Amp dual circuit breaker, Q1515
15 Amp circuit breaker, Q115
2-155