TM 5-3610-287-24
SYMPTOM INDEX (CONT)
Troubleshooting
Procedure
Page
WALL OUTLET
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..
Does not operate
Does not operate
WALL HEATER
Does not operate
Blows cold air
Heat rises but fan does not operate
Circuit breaker continually trips . . . . . . . . . . . . . . . . . . . . . .
PRESS
Does not operate
Organizational Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
EMERGENCY LIGHT SET INDICATOR LAMP DOES NOT LIGHT WHEN PLUGGED IN.
Check that circuit breaker is ON.
Step 1.
Set circuit breaker to ON.
WARNING
HIGH VOLTAGE. When working on high voltage
components, always have an additional person
present. Keep one hand away from equipment to
reduce hazard of current flowing through vital
organs of body. Remove all jewelry from
fingers, wrists, and neck before working on
electrical components. Failure to observe this
warning may result in death or serious burns.
Step 2. Check voltage at emergency light wall outlet. Reading
should be 110 5 Vac.
Troubleshoot wall outlet (malfunction 20).