TM 5-3610-287-24
Organizational Troubleshooting (Cont)
Table 2-3.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
20.
WALL OUTLET DOES NOT OPERATE.
Step 1.
Check that appropriate circuit breaker is ON.
Set appropriate circuit breaker to ON.
WARNING
HIGH VOLTAGE. When working on high voltage
components, always have an additional person
present. Keep one hand away from equipment to
reduce hazard of current flowing through vital
organs of body. Remove all jewelry from
fingers, wrists, and neck before working on
electrical components. Failure to observe this
warning may result in death or serious burns.
Step 2.
Set appropriate circuit breaker to OFF. Remove cover plate
and partially remove outlet. Set circuit breaker to ON.
Test voltage across outlet terminals. Reading should be
110 --
+10 Vac.
If reading is not correct and if defective wall outlet
is in expanding side wall, go to next step.
If reading is not correct and if defective wall outlet
is in Section wall, troubleshoot appropriate circuit
breaker (malfunction 14).
Step 3.
Remove cover from expanding side power cable junction box.
Test voltage across terminals of wires marked W and 18
(curbside) or W and 22 (roadside). Reading should be 110
10 Vac.
If reading is correct , refer equipment to depot
maintenance for repair of internal wiring.