TM 5-3610-257-14
d.
Desolder connections and remove defective valve.
CAUTION
Use care when removing or installing valve to avoid damaging sensing tube.
e.
Loosen clips and remove sensing bulb from refrigerant line.
f.
Reinstall sensing bulb to refrigerant line.
g.
Install new valve and solder connections.
h.
Evacuate refrigerant lines and recharge with freon R-12.
i.
Reinstall covers.
j.
Plug in power cord.
5-52