TM 5-3610-257-14
a.
Unplug power cord.
b.
Loosen retaining screws and remove front cover.
c.
Disconnect wiring to compressor motor.
d.
Remove four mounting screws from base.
e.
Evacuate refrigerant from system.
f.
Desolder refrigerant lines from defective compressor assembly and remove.
g.
Install new compressor and solder refrigerant lines.
h.
Reinstall mounting screws.
i.
Evacuate refrigerant lines and recharge system with freon R-12.
j.
Reconnect wiring to compressor motor.
k.
Reinstall front cover and retaining screws.
l.
Plug in power cord.
5-50