TB 1-4920-443-35
62. T700 Inlet Guide Vane Position
a. Performance Check
Note: AEDATS Alignment See Calibration of Automatic Data Acquisition H355-7 (AEDATS
IV) for FEDS Alignment requirements.
(1) The TI will request the channel name. Enter IGV, then press the return key.
(2) The TI
AEDATS II
screen will request the first calibration point. Do
not enter a
value at
this time. (The
TI AEDATS II screen will display an input range of 0.0 to 8.0 VDC and an output range of 0 to 90%).
(3) Disconnect TI plug P53.
(4) Connect the Voltage Calibrator to the TI plug P53, pins A (+) and B (-), observing polarity.
(5) Set Voltage Calibrator output controls for 0.00 VDC.
(6) Enter 0 as the first TI AEDATS II Alignment point, then press the return key. After 0 is entered, the TI
AEDATS II screen will request the second calibration point. Do not enter a value at this time.
(7) Set the vertical scale ZERO control for a TI indication of 0 deg.
(8) Set the Voltage Calibrator output controls for 8.00 VDC.
(9) Set the vertical scale SPAN control for a TI indication of 90%.
(10) Enter 90% as the second AEDATS II Alignment point, then press the return key. After 90% is
entered, the TI AEDATS II screen will request satisfactory Y/N? Do not make a selection at this time.
(11) Set Voltage Calibrator output controls for the values listed.
(12) The TI AEDATS II screen and the Vertical Scale must indicate within the corresponding values listed.
(13) Record results.
(14) After the last test point, enter Y to satisfy the AEDATS II screen request for satisfactory Y/N? then
press the return key.
Table 62-1 IGV
Voltage Input
AEDATS 4
Vertical Scale
(VDC)
IGV
Bottom Row #4
(0.5%)
Indicator (1.0 deg)
0 (10%)
2 (15%)
4 (40%)
6 (65%)
8 (90%)
(15)Set the Voltage Calibrator for minimum output.
(16)Disconnect the Voltage Calibrator from TI plug P53.
(17)Reconnect TI plug P53