TM 5-6675-318-14
Table 1-5. DIRECT/GENERAL SUPPORT TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
RECEPTACLES DO NOT OPERATE BUT CIRCUIT BREAKERS ARE ON - Cont
Step 2.
C h e c k to see if voltage meter and frequency scale and INCORRECT
PHASE or CORRECT PHASE lamp indicate necessary power.
Notify your supervisor for service of power supply at source.
5.
CIRCUIT BREAKERS TRIP CONTINUALLY .
WARNING
Turn off and padlock safety switch before inspecting or servicing
F a i l u r e to do so may result in
death or serious injury.
Step 1.
Check to see if receptacles are overloaded.
S t e p 2.
Check to see if receptacles are damaged.
1-20. MAINTENANCE PROCEDURES.
a. This section contains instructions covering direct/general support maintenance
Personnel required are listed only if the task
functions for the Survey Section.
requires more than one.
sure that equipment is properly functioning.
1-80