TM 5-3610-287-24
2-48. REPAIR POWER ENTRY PANEL ASSEMBLY (CONT)
15.
Install power input cables (3) and wires (4) on main power switch
terminal block. Secure terminal block screws (5).
16.
Close main power switch door.
17.
Install power entry panel cover (2) with screws (1), lockwashers, and
flatwashers.
WARNING
ELECTRICAL HAZARD. Do not connect power cable to Section
before grounding. Failure to observe this warning may
result in death or serious injury.
18.
Ensure Section is grounded, then connect main power cable.
19.
Test phase and voltage at power monitor assembly (TM 5-3610-287-10,
20.
To test operate, set MAIN POWER switch and MAIN and auxiliary circuit
breakers to ON and ensure lighting and outlets are operational.
21.
If necessary, paint main power receptacle in accordance with
TM 43-0139.
DC POWER RECEPTACLE
INITIAL SETUP
Tools
Light machine repair tool kit (appendix B, section III, item 11)
Cross-tip screwdriver
Flat-tip screwdriver
Combination wrench set
Extension light
Materials/Parts
Dc power receptacle, MS3102A-16-10P
2-140