Table 4-2. UNIT TROUBLESHOOTING
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4-19. NO POWER TO MICROFIX RECEPTACLE.
WARNING
Use extreme caution when performing checks or maintenance at or near power entrance box and power
distribution box. Failure to do so may result in death or serious injury.
Check voltage at receptacle with multimeter.
If 120v does not exist, check circuit breaker for continuity. If continuity exists, replace receptacle (refer
to paragraph 4-26). If no continuity at circuit breaker, replace circuit breaker (refer to paragraph 4-24).
4-11