TM 5-6675-318-14
Table 5-3. DIRECT/GENERAL SUPPORT TROUBLESHOOTING
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
NO CHARGING CURRENT
Step 1. Remove
(a)
( b)
IS INDICATED ON AMMETER.
fuse and check for continuity.
I f c o n t i n u i t y e x i s t s , p r o c e e d t o s t e p 2 .
If continuity does not exist, replace fuse (paragraph
5 - 1 0 . 1 ) .
Step 2.
Check power outlet for 120 V ac using a multimeter.
(a) If power is present, proceed to step 7.
(b) If power is not present, proceed to step 3.
Step 3.
Check power panel indicators for correct voltage, frequency, and
phase.
( a ) I f c o r r e c t , p r o c e e d t o s t e p 4 .
( b ) I f i n c o r r e c t , n o t i f y p o w e r s u p p l y s u p e r v i s o r .
Step 4.
C h e c k c i r c u i t b r e a k e r o n / o f f p o s i t i o n.
( a ) I f c i r c u i t b r e a k e r
( b ) I f c i r c u i t b r e a k e r
( c ) I f c i r c u i t b r e a k er
s u p e r v i s o r .
is on, proceed to step 5.
i s o f f , t u r n o n .
t r i p s r e p e a t e d l y , n o t i f y p o w e r s u p p ly
5-13