TM 5-6675-315-14
WARNING
To prevent death or serious injury, do not handle or clean power cable or connectors when cable
is connected to power source.
NOTE
The section must be properly grounded before power is connected. If it is not possible to drive
the three sections of grounding rod fully into ground, the rods may each be driven into the
ground separately and connected in series. If it is impossible to drive a grounding rod, a
suitable alternative ground must be found, such as a buried metal water pipe. See TC 11-6,
Grounding Techniques for additional instructions.
(11)
Connect grounding cable to grounding lug with wing nut.
CAUTION
Be sure safety switch is off before connecting power cable to avoid equipment damage.
(12)
Firmly connect the power cable to the power receptacle.
1-30