TM 5-3610-287-24
Table 2-3.
Organizational Troubleshooting (Cont)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
15.
CIRCUIT BREAKER CONTINUALLY TRIPS.
WARNING
q Turn
off main power switch before performing
this task. Failure to do so may result in
death or serious injury.
q HIGH
VOLTAGE. When working on high voltage
components, always have an additional person
present. Keep one hand away from equipment
to reduce hazard of current flowing through
vital organs of body. Remove all jewelry
from fingers, wrists, and neck before
working on electrical components. Failure
to observe this warning may result in death
or serious burns.
Set MAIN POWER switch to OFF. Remove circuit breaker cover panel.
Remove wire(s) from suspected circuit breaker. If circuit breaker
has more than one pole, remove one wire at a time. Set MAIN POWER
switch to ON. Set suspected circuit breaker to ON.
If circuit breaker still trips, replace circuit breaker
If circuit breaker does not trip, troubleshoot appropriate
appliance, lights, or wiring.
16.
BLACKOUT LIGHTS COME ON WHEN BLACKOUT LIGHTS SYSTEM IS ACTIVATED.
Check, that both personnel doors are closed.
Step 1.
Close personnel doors.