TM 5-6675-326-14
1-6.1 Assembly and Preparation for Use - Continued
(9) Connect other end of ground cable to ground lug in power entry panel.
g.
Connect power cable to power cable jack in power entry panel.
CAUTION
Be sure safety switch is ON before setting main circuit breaker ON. Do not turn
power on in van if incorrect phase lamp comes on. Damage to equipment may
result.
h.
Check voltage and frequency.
(1) Push down PHASE TEST button.
(2) Observe CORRECT PHASE or INCORRECT PHASE lights.
(3) Turn PHASE switch to A.
(4) Read voltage on meter.
NOTE
Voltage must be between 110 and 125 vac.
(5) Read frequency on scale.
NOTE
Frequency must be 60 + 1 Hz.
Change 1