TM 5-6675-323-14
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
NO POWER TO EQUIPMENT - Cont
(c)
If circuit breaker
trips
repeatedly,
notify
power
supply
supervisor.
S t e p 2.
(a) If input voltage is present, proceed to step 3.
(b) If input voltage is not present, refer to direct/general
support maintenance for repair or replacement of defective
wiring.
Check circuit breaker output for 120 V ac.
Step 3.
(a) If output voltage is present, proceed to step 4.
(b) If output voltage is not present, refer to direct/general
S t e p 4.
R e m o v e receptacle and check for 120 V ac input.
(b) If not present, refer to direct/general support maintenance
for repair or replacement of defective wiring.
1-59