TM 5-6675-318-14
Table 1-4. ORGANIZATIONAL TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
FLUORESCENT CEILING LAMP IS INOPERATIVE - Cont
1.
S t e p 3.
Check for shorts in RF filter.
2.
(a)
If
(b) If continuity does not exist, replace switch (paragraph 1-
16.4).
EMERGENCY LIGHTS ARE INOPERATIVE.
3.
Press in test indicator.
I f lamps do not light, replace emergency light assembly (paragraph
NO POWER TO EQUIPMENT.
4.
Step 1.
Check circuit breaker ON/OFF position.
(c) If circuit breaker trips repeatedly, notify power supply
supervisor.
Step 2.
Check circuit breaker input for 120 V ac.
(a) If input voltage is present, proceed to step 3.
(b) If input voltage is not present, refer to direct/general
support maintenance for repair or replacement of defective
wiring.
1-51