TM 5-3610-259-14
11. Firmly connect the
Be sure safety
power cable to
power cable to the power receptacle.
CAUTION
switch is off before connecting
avoid equipment damage.
l
l
Push phase test button.
Observe correct phase lamp lights.
CAUTION
DO NOT ENERGIZE SECTION IF INCORRECT PHASE LAMP
LIGHTS .
DAMAGE TO EQUIPMENT MAY RESULT.
VOLTAGE MUST BE BETWEEN 110 AND 120, AND FREQUENCY
MUST BE AT 60 +1 HZ ON EACH LEG BEFORE TURNING ON
MAIN CIRCUIT BREAKER OR DAMAGE TO EQUIPMENT MAY
RESULT.
l
Turn phase switch to A.
l
Read voltage on meter.
l
Read frequency on scale for 60 +1 Hz.
l
Repeat for positions B and C on phase switch.
1-36