TM 5-3610-257-14
CAUTION
Use care when removing sensing bulb to avoid damaging sensing tube.
d.
Remove retaining clips and cabinet grommet. Carefully remove sensing bulb and tube from cabinet.
e.
Tag and remove wiring from thermostat switch terminals.
f.
Loosen retaining screws and remove defective thermostat.
g.
Install new thermostat and tighten retaining screws.
h.
Reinstall electrical wiring to thermostat switch terminals in proper reassembly order.
i.
Using care to avoid damaging sensing tube, insert sensing bulb and tube through cabinet wall and retain with
clips.
j.
Reinstall thermostat cover and tighten retaining screws.
k.
Adjust thermostat to 60F (15.6C).
l.
Reinstall front cover and tighten retaining screws.
m.
Plug in power cord.
5-33