Table 1-5. DIRECT/GENERAL SUPPORT TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4. RECEPTACLES DO NOT OPERATE BUT CIRCUIT BREAKERS ARE ON - Cont
Check to see if voltage meter and frequency seal e and INCORRECT
Step 2.
PHASE or CORRECT PHASE lamp indicate necessary power.
Notify your supervisor for service of power supply at source.
5. CIRCUIT BREAKERS TRIP CONTINUALLY.
WARNING
Turn off and padlock safety switch before inspecting or servicing
circuit breakers or receptacles. Failure to do so may result in
death or serious injury.
Step 1.
Reconnect equipment to different receptacles.
Step 2.
1-20. MAINTENANCE PROCEDURES.
This section contains instructions covering direct/general support maintenance
functions for the Finishing Section. Personnel required are listed only if the task
requires more than one.
b. After completing each maintenance procedure, perform operational check to be
sure that equipment is properly functioning.
1-88