TM 5-3610-253-14
CAUTION
Do not energize section if incorrect phase lamp lights. Damage to equipment
may result.
Observe correct phase lamp lights.
(a) Push phase test switch.
(b) Turn phase switch to A.
CAUTION
Voltage must be between 110 and 120, and frequency must be at 60 1 Hz
on each leg before turning on main ci rcuit breaker or damage to equipment
may result.
(c) Read voltage on meter.
(d) Read frequency on seal e.
(e) Repeat for positions B and C on phase switch.
(15) Set main circuit breaker ON.
1-32