TM 5-6675-328-14
Table 1-5. DIRECT/GENERAL SUPPORT TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
RECEPTACLES DO NOT OPERATE BUT CIRCUIT BREAKERS ARE ON.
WARNING
Turn off main circuit breaker before inspecting or servicing circuit breakers or receptacles. Failure to do
so may result in death or serious injury.
Step 1.
Check to see if power cable is firmly connected to power entry panel.
Connect power cable.
Step 2.
Check to see if voltage meter and frequency scale and INCORRECT PHASE or CORRECT PHASE
lamp indicate necessary power.
Notify your supervisor for service of power supply at source.
5.
CIRCUIT BREAKERS TRIP CONTINUALLY.
WARNING
Turn off main circuit breaker before inspecting, or servicing circuit breakers, or receptacles. Failure to do
so may result in death or serious injury.
Step 1.
Check to see if receptacles are overloaded.
Reconnect equipment to different receptacles.
Step 2.
Check to see if receptacles are damaged.
Replace receptacles (paragraph 1-16.6).
1-90