TM 5-6675-325-14
Table 1-4. ORGANIZATIONAL TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
2 .
3 .
FLUORESCENT CEILING LAMP IS INOPERATIVE - Cont
Step 2.
Check for continuity of lamp ballast.
( a ) I f c o n t i n u i t y e x i s t s , p r o c e e d t o s t e p 3.
(b) If continuity does not exist, replace lamp ballast (paragraph
1 - 1 6 . 1 ) .
Step 3.
Check for shorts in RF filter.
Replace RF filter (paragraph 1-16.2).
EXHAUST FAN IS INOPERATIVE.
Check on/off switch for continuity.
( a ) I f c o n t i n u i t y e x i s t s , r e p l a c e f a n ( p a r a g r a p h 1 - 1 6 . 9 ) .
(b) If continuity does not exist, replace switch (paragraph
1 - 1 6 . 4 ) .
EMERGENCY LIGHTS ARE INOPERATIVE.
P r e s s i n t e s t i n d i c a t o r.
If lamps do not light, replace emergency light assembly (paragraph
1 - 1 6 . 1 1 ) .
1-59