TM 5-6675-317-14
Table 1-5. DIRECT/GENERAL
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
SUPPORT TROUBLESHOOTING- Cent
4.
RECEPTACLES DO NOT OPERATE BUT CIRCUIT BREAKERS ARE ON - Cont
Step 2.
Check to
PHASE or
Notify
see if voltage meter and frequency scale and INCORRECT
CORRECT PHASE lamp indicate necessary power.
your supervisor for service of power supply at source.
5.
CIRCUIT BREAKERS TRIP CONTINUALLY.
WARNING
Turn off and padlock safety switch before inspecting or servicing
circuit breakers or receptacles.
Failure to do so may result in death or
serious injury.
Step 1.
Check to see if receptacles are overloaded.
Reconnect equipment to different receptacles.
Step 2.
Check to see if receptacles are damaged.
Replace receptacles (paragraph 1-16.5).
1-90