TM 5-6675-313-14
Table 1-4. ORGANIZATIONAL TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
NO POWER TO EQUIPMENT - Cont
Step 2.
Check circuit breaker input for 120 V ac.
(a) If input voltage is
(b) If input voltage is
support maintenance
wiring.
present, proceed to step 3.
not present, refer to direct/general
for repair or replacement of defective
Step 3.
Check circuit breaker output for 120 V ac.
(a) If output voltage is present, proceed to step 4.
(b) If output voltage is not present, refer to direct/general
support maintenance for circuit breaker replacement
(paragraph 1-20.5).
Step 4.
Remove receptacle and check for 120 V ac input.
(a) If present, replace receptacle (paragraph 1-16.6).
(b) If not present, refer to direct/general support maintenance
for repair or replacement of defective wiring.
1-58