TM 5-6675-313-14
Table 1-4. ORGANIZATIONAL TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
FLUORESCENT CEILING LAMP IS INOPERATIVE - Cont
Step 2.
Check for continuity of lamp ballast.
(a) If continuity exists, proceed to step 3.
(b) If continuity does not exist, replace lamp bal last ( paragraph
1-16.1).
Step 3.
Check for shorts in RF Filter.
Replace RF filter (paragraph 1-16.2).
2.
VENTILATION FAN IS INOPERATIVE.
Check on/off switch for continuity.
(a) If continuity exists,
replace fan (paragraph 1-16.9).
(b) If continuity does not exist, replace switch (paragraph
1-16.4).
3.
EMERGENCY LIGHTS ARE INOPERATIVE.
Press in test indicator.
If lamps do not light, replace emergency light assembly (paragraph
1-16.11).
4.
NO POWER TO EQUIPMENT.
Step 1.
Check circuit breaker ON/OFF position.
(a) If circuit breaker is ON, proceed to step 2.
(b) If circuit breaker is OFF, turn ON.
(c) If circuit breaker trips repeatedly, notify power supply
supervisor.
1-57