TM 5-6675-324-14
Table 4-4. ORGANIZATIONAL TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
3. OVER OR UNDERCOMPENSATION FOR TEMPERATURE RISE.
Step 1.
perature 68F (20C) should be 106.7 k ohms 10%.
(a) If thermistor is good, proceed to step 2.
Step 2.
Check for free and correct operation of blower unit as follows:
(b) Connect meter leads to blower motor supply leads.
4-53