TM 5-6675-323-14
Table 1-5. DIRECT/GENERAL SUPPORT TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
RECEPTACLES DO NOT OPERATE BUT CIRCUIT BREAKERS ARE ON.
WARNING
Turn off main circuit breaker before inspecting or servicing circuit breakers
or receptacles.
Failure to do so may result in death or serious injury.
S t e p 1.
C h e c k to see if power cable is firmly connected to power entry
panel.
C o n n e c t power cable.
S t e p 2.
C h e c k to see if voltage meter and frequency scale and INCORRECT
PHASE or CORRECT PHASE lamp indicate necessary power.
Notify your supervisor for service of power supply at source.
5.
CIRCUIT BREAKERS TRIP CONTINUALLY.
WARNING
Turn off and padlock safety switch before inspecting or servicing
Failure to do so may result in
death or serious injury.
Step 1.
Check to see if receptacles are overloaded.
Check to see if receptacles are damaged.
S t e p 2.
1-89