TM 5-6675-320-14
( 5 ) E n t e r s e c t i o n a n d b e s u r e s a f e t y s w i t c h , m a i n c i r c u i t b r e a k e r , a n d a ll
e q u i p m e n t p o w e r s u p p l y s w i t c h e s a r e o f f .
WARNING
Death or serious injury may occur from connecting power cable to section
before grounding.
(6) Remove ground rod, slide hammer, and ground cable from section.
NOTE
l Apply a thin film of grease to threaded ends of rods before driving into
ground. This will permit easy disassembly upon removal from ground.
l Bottom ground rod must be numbered or identified so that it will always
be the first rod driven into the ground.
l These instructions supplement TC 11-6, Grounding Techniques.