TM 5-6675-318-14
a.
Turn off and padlock safety switch.
b. Remove conduit cover.
c.
Inspect wires for damage.
NOTE
Refer to direct/general support maintenance for wiring repair if necessary.
d.
Loosen wiring and carefully pull it from the entire base section.
e.
Remove screws and base from wall.
f . Mark and measure damaged area on molding. Record measurement.
C u t damaged area from molding.
g.
h. Cut section from new molding to the length recorded in step f.
i.
U s i n g damaged area as a template, mark mounting holes on new piece.
With a number 25 drill bit, drill holes in new molding.
j.
k. With file, remove all burred edges.
Paint base section as required.
l.
m.
Reinstall conduit base on wall with screws.
n.
Carefully place wiring back in conduit base.
Reinstall cover on base.
o.
Test wiring for continuity between power wires and conduit. If there is
p.
continuity, determine and correct grounding fault.
Test wiring with power on.
q.
1-65