TM 5-6675-318-14
Table 1-2. TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
NO ELECTRICAL POWER TO SECTION - Cont
1.
Step 1.
O b s e r v e voltage and frequency for phases A, B, and C. Read 115
5V, 60 1 Hz.
(a) If voltage and frequency are correct, proceed to step 2.
(b) If voltage and frequency are incorrect, notify power supply
supervisor.
CAUTION
Do not energize section if voltage or frequency is not correct. Damage
t o equipment may result.
S t e p 2.
P r e s s phase test switch on power panel for A, B, and C.
(a) If phases A, B, and C are correct, proceed to step 3.
(b) If incorrect phase lamp lights, notify power supply
supervisor.
CAUTION
Do not energize section if incorrect phase lamp lights.
Damage to equipment
may result.
Step 3.
Check safety switch position.
(a) If safety switch is ON, proceed to step 4,
(b) If safety switch is OFF, turn ON.
Step 4.
(a) If circuit breaker is ON, refer to direct/general support
maintenance.
(c) If circuit breaker trips repeatedly, notify power supply
supervisor.
1-40