TM 5-6675-317-14
(13) Turn on safety switch.
CAUTION
DO not energize section if incorrect phase lamp lights. Damage to equipment
may result.
(14) Check voltage and frequency as follows:
(a) Push phase test switch.
Observe correct phase lamp lights.
(b) Turn phase switch to A.
CAUTION
Voltage must be between 110 and 120 and frequency must be at 60 ±1 Hz
on each leg before turning on main circuit breaker or damage to equipment
may result.
(C) Read voltage on meter.
(d) Read frequency on scale.
(e) Repeat for positions B and C on phase switch.
1-32