TM 5-6675-315-14
Table 1-4. ORGANIZATIONAL TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. FLUORESCENT CEILING LAMP IS INOPERATIVE - Cont
Step 2. Check for continuity of lamp ballast.
(a)
If continuity exists, proceed to step 3.
(b)
If continuity does not exist, replace lamp ballast (paragraph 1-16.1).
Step 3. Check for shorts in RF filter.
Replace RF filter (paragraph 1-16.2).
2. VENTILATION FAN IS INOPERATIVE.
Check ON/OFF switch for continuity.
(a)
If continuity exists, replace fan (paragraph 1-16.8).
(b)
If continuity does not exist, replace switch (paragraph 1-16.4).
3. EMERGENCY LIGHTS ARE INOPERATIVE.
Press in test indicator.
If lamps do not light, replace emergency light assembly (paragraph 1-16.10).
4. NO POWER TO EQUIPMENT.
Step 1. Check circuit breaker ON/OFF position.
(a)
If circuit breaker is on, proceed to step 2.
(b)
If circuit breaker is off, turn on.
(c)
If circuit breaker trips repeatedly, notify power supply supervisor.
1-58