Table 1-5. DIRECT/GENERAL SUPPORT TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4. RECEPTACLES DO NOT OPERATE BUT CIRCUIT BREAKERS ARE ON - Cont.
Step 2.
5. CIRCUIT
Check to see if voltage meter and frequency seal e and INCORRECT
PHASE or CORRECT PHASE lamp indicate necessary power.
Notify your supervisor for service of power supply at source.
BREAKERS TRIP CONTINUALLY.
WARNING
Turn off and padlock safety switch before
circuit breakers or receptacles.
Fai 1 ure
death or serious injury.
inspecting or servicing
to do so may result in
Step 1.
Check to see if receptacles are overloaded.
Reconnect equipment to different receptacles.
Step 2.
Check to see if receptacles are damaged.
Replace receptacles (paragraph 1-16.6)
1-20. MAINTENANCE PROCEDURES.
This section contains Instructions covering direct/general support maintenance
functions for the Storage and Distribution Section.
Personnel required are listed
only if the task requires more than one.
b. After completing each maintenance procedure, perform operational check to be
sure that equipment is properly functioning.
1-87