TM 5-6675-314-14
Table 1-4. ORGANIZATIONAL TROUBLESHOOTING - Cont
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
4.
NO POWER TO EQUIPMENT - Cont
Step 2.
Check circuit breaker input for 120 V ac.
(a) If input voltage is present, proceed to step 3.
( b ) I f i n p u t v o l t a g e i s n o t p r e s e n t , r e f e r t o d i r e c t / g e n e r a l
support maintenance for repair or replacement of defective
w i r i n g .
Step 3.
Check circuit breaker output for 120 V ac.
(a) If output voltage is present, proceed to step 4.
( b ) I f o u t p u t v o l t a g e i s n o t p r e s e n t , r e f e r t o d i r e c t / g e n e r al
support maintenance for circuit breaker replacement
(paragraph 1-20.5).
Step 4.
Remove receptacle and check for 120 V ac input.
(a) If present, replace receptacle (paragraph 1-16.6) .
(b) If not present, refer to direct/general support maintenance
for repair or replacement of defective wiring.
1-56