TM 5-3610-259-14
WARNING
l
l
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
DEATH OR SERIOUS INJURY MAY RESULT FROM
FAILURE TO TURN OFF SAFETY SWITCH BEFORE
REPAIRING CABLE RUNS.
A qualified
NOTE
electrician should perform this task.
Auxiliary lighting
procedure.
may be required for this
Turn off safety switch and secure with padlock.
Determine general area of fault or damage.
Remove conduit base cover.
Inspect wires for damage.
Repair or replace any damaged wires as
required.
Inspect conduit base for damage.
If damage has occurred, proceed to
the next step, otherwise go to step 18.
Loosen wiring and carefully pull it from the entire base section.
Remove screws and conduit base.
Measure damaged area and record readings.
Cut damaged area from base.
Cut new base section to the length recorded in step 8.
Using damaged area as a template, mark mounting holes on new piece.
With a number 25 drill bit, drill holes where marks were placed on
new piece.
With file, remove all burred edges.
Paint base section as required.
Reinstall conduit base with screws on wall.
Carefully place wire back in conduit base.
If conduit base cover is damaged, proceed to the next step, other-
wise go to step 22.
Measure damaged area and record reading.
1-135