TM 5-3610-257-14
WARNING
To prevent death or serious injury, do not handle or clean power cable or connectors when cable
is connected to power source.
NOTE
The section must be properly grounded before power is connected. If it is not possible to drive
the three sections of ground rod fully into ground, the rods may each be driven into the ground
separately and connected in series. If it is impossible to drive a ground rod, a suitable alternative
ground must be found, such as a buried metal water pipe. See TC 11-6, Grounding Techniques for
additional instructions.
(11)
Connect ground cable to ground lug with wingnut.
1-36